How to enable output from PLCS Analog module
2014.06.11

Q: There is no output value from PLCS DA(Analog Output) module. 


A: Unlike CP and XP PLC, Channel of PLCS must be enabled to use output signal. 


 


 


[Setting] 


  


HELP PLCS DA Module 


 



 


 


[Tip] 


Output signal Y03, Y04, Y05 and Y06 works properly when those are turned ON.  



 


Write slot number as above. 


  


-Example- 


If Analog Output (DA) or Analog Mixed I/O (ADDA) module is installed next to CPU, its output number is Y23 because PLCS CPU occupies 32 points input and output already. 


 



       If DA or ADDA module is installed next to CPU, Enable Y23 ~ Y26 to make 4 channels output properly.  


 


 


For more details, download below manual.