 A. CIMON PLC uses 17 differently named devices.  

     Each device has its own symbol and is denoted by a capital character.   

  

       

  

X Device (Bit / Input) 

  

– X device is an input contact that receives a signal from the input module. 

– It accepts the signal from the input device such as a push button switch or limit switch. 

– Since the input status of X device is stored inside the PLC, a user can use A and B contacts.  

– If used as a word type, X device can be used according to the bit device’s word usage. 

– It is a read-only device that a user cannot enter a value. 

– X Device Allocation for PLC modules (Input and special modules) other than CPU: 

 

1.          PLC card occupies 16 points (1 Word). 

2.          Input card with 16 points or less: occupies 16 points (1 Word). 

3.          Input card with 32 points: occupies 32 points (2 Word). 

4.          Special cards other than input cards occupy 16 points (1 Word).  

 

Example) 

 

 

Turning on X00 device will output Y20.    

 

 

 

  Y Device (Bit / Output) 

 

– Y device is an output contact that delivers the operation result to output devices such as solenoid valves, motors and lamps. 

– If used as a word type, Y device can be used according to the bit device’s word usage.  

– Y device can only use and output Contact A. 

– Y Device Allocation for PLC modules (Output and special modules) other than CPU: 

 

1.         PLC card occupies 16 points (1 Word). 

2.         Output card with 16 points or less: occupies 16 points (1 Word). 

3.         Output card with 32 points: occupies 32 points (2 Word). 

4.         Special cards other than output cards occupy 16 points (1 Word).

 

Example)

 

 

Turning on X00 device will output Y20.

 

 

 

 

M Device (Bit / Internal Auxiliary Relay) 

 

– M device is an internal input and output digital device that cannot output the operation result to external devices. But the output in connection with I/O contacts can be made possible. 

– It can be used in applications such as intermediate data storage, virtual I/O and word data storage. 

– M device can use Contact A and B.

  

Example)

 

 

  

Turning on X00 device will turn on M20. SET instruction keeps M20 ON even if X00 turns OFF.

 

 

 

  

L Device (Bit / Link Relay) 

 

 L device can be used as a special contact for computer link and data link modules. 

– If not used as a link, L device can be used as same as M device. 

– If used as a word type, L device can be used according to the bit device’s word usage.

 

Example)

 

     

Turning on L00 device will send Frame No. 0 of the
Program ID No. 1 and saves the sending result in M100 device.



  

* For the rest of the 13 PLC Devices, please refer to the attached PDF file.